Voltage Drop Calculator

This voltage drop calculator works out the voltage lost along a copper or aluminum wire from the wire size, current, voltage and one-way length, for DC, single-phase and three-phase circuits.

Restored your last values ·

Enter the one-way distance from the panel or source to the load; the calculator counts the return conductor for you.

Everything is worked out in your browser. Nothing you type is sent anywhere.

Voltage drop

–

Enter the voltage, current and wire length.

See full result

A voltage drop calculator works out how much voltage is lost along a run of wire, so you can check that a circuit delivers enough voltage to the equipment at the far end. Choose the wire size and whether it's copper or aluminum, enter the source voltage, the load current and the one-way length, and this voltage drop calculator gives the drop in volts, the percentage of the source voltage, the voltage left at the load and the power wasted as heat. US wire sizes in AWG and lengths in feet are the default, with metric sizes in mm² and meters.

Why voltage drops along a wire

Every wire has a little resistance, and current flowing through resistance loses voltage (Ohm's law: V = I × R). On a long run or with heavy current, that loss adds up: lights look dim, motors run hot and struggle to start, and electronics may misbehave. Thicker wire has less resistance, which is why long runs often need a larger wire size than the current alone would suggest.

The voltage drop formula

For a DC or single-phase AC circuit, current flows out along one conductor and back along the other, so the length counts twice:

Voltage drop = 2 × one-way length × current × resistance per unit length

For a balanced three-phase circuit, the factor is √3 (about 1.732) instead of 2. The percentage drop is the drop divided by the source voltage, times 100, and the power lost in the wire is the current squared times the total resistance.

Wire resistance

For AWG sizes, the calculator uses the resistance of copper wire per foot from the standard AWG table: for example 2.525 mΩ per foot for 14 AWG, 1.588 for 12 AWG, 0.9989 for 10 AWG and 0.6282 for 8 AWG. Larger numbers are thinner wires, and sizes above 1 AWG are written 1/0, 2/0, 3/0 and 4/0.

For metric sizes, it works out the resistance from the cross-section and the resistivity of the metal: copper is 1.68 × 10⁻⁸ ohm-meters and aluminum is 2.82 × 10⁻⁸ ohm-meters. Because aluminum's resistivity is about 1.68 times copper's, an aluminum conductor needs a larger size to carry the same current with the same drop, and the calculator scales the AWG figures by that ratio when you choose aluminum.

Worked example: a 100 ft branch circuit

A 120 V single-phase circuit feeds a 15 A load 100 feet away on 12 AWG copper.

  1. Resistance: 1.588 mΩ per foot.
  2. Drop: 2 × 100 × 15 × 0.001588 = 4.76 V.
  3. Percent: 4.76 ÷ 120 = 3.97%.
  4. Voltage at the load: about 115.2 V.

Moving up to 10 AWG cuts the drop to 2 × 100 × 15 × 0.0009989 ≈ 3.00 V, or 2.50%.

Worked example in metric

A 230 V circuit carries 16 A over 30 meters on 2.5 mm² copper. The resistance is 1.68 × 10⁻⁸ ÷ 2.5 × 10⁻⁶ = 0.00672 ohms per meter, so the drop is 2 × 30 × 16 × 0.00672 ≈ 6.45 V, or about 2.8% of 230 V.

How to use the voltage drop calculator

  1. Choose US or metric units and the circuit type.
  2. Pick copper or aluminum and the wire size.
  3. Enter the source voltage and the load current.
  4. Enter the one-way length from the source to the load.
  5. Press Calculate, then try a bigger wire if the drop is too high.

What drop is acceptable?

How much drop is acceptable depends on your local electrical code and on the equipment. Many designers aim to keep the drop small, a few percent at most, so that equipment gets close to its rated voltage. The result turns orange above 5% as a prompt to look at a larger wire, a shorter run or a higher supply voltage. Check your code and the equipment's specifications for the limit that applies.

Low-voltage circuits

Voltage drop matters most at low voltages. A 12 V DC run to an RV, a boat or landscape lighting loses the same volts as a 120 V run with the same current and wire, but those volts are a much bigger share of 12. That's why low-voltage systems often need surprisingly thick cable.

Choosing a wire size

To pick a wire for a new circuit, start with the size your local code requires for the current, then check the voltage drop for the length of the run. If the drop is higher than you want, try the next size up and calculate again. Going from 12 AWG to 10 AWG, for example, cuts the resistance by more than a third. On very long runs, such as to a garage, a well pump or an outbuilding, it's common for voltage drop rather than current to decide the wire size.

Remember that a larger wire may need different connectors, a larger conduit or a breaker that accepts it. Plan those details with an electrician before you buy cable.

Solar and battery systems

Solar panels, batteries and inverters often run at 12, 24 or 48 V DC with high currents, so even a short cable can waste a noticeable share of the energy. Use the DC setting and the actual current, and keep runs between batteries and inverters as short and thick as practical.

Common mistakes

  • Entering the round-trip length. Enter the one-way distance; the return is included.
  • Forgetting aluminum's higher resistance.
  • Sizing only for current. Long runs often need a bigger wire for voltage drop.
  • Ignoring temperature. Hot conductors have more resistance than the table shows.

What next

Use this often? Add Voltage Drop to your Home screen.

Frequently asked questions

How does the voltage drop calculator work?

It multiplies 2 × the one-way length × the current × the wire's resistance per unit length (or √3 instead of 2 for three-phase), then divides by the source voltage for the percentage.

What is the voltage drop for 12 AWG wire at 100 feet?

At 15 A on a 120 V single-phase circuit, about 4.76 V, or 3.97%.

Does aluminum wire have more voltage drop?

Yes. Aluminum's resistivity is about 1.68 times copper's, so the same size drops more voltage.

Should I enter the one-way or total length?

The one-way distance from the source to the load. The calculator counts the return conductor.

How do I reduce voltage drop?

Use a larger wire, shorten the run, lower the current or use a higher supply voltage.