A three-phase motor amperage calculator estimates the current that a three-phase motor draws at full load. Enter the rated output in horsepower or kilowatts, the line voltage, the efficiency and the power factor, and it gives the current in each line and the input power in kilowatts and kilovolt-amperes.
How to use the three-phase motor amperage calculator
- Choose the unit and enter the motor's rated output.
- Enter the line voltage, the efficiency and the power factor.
- Press Calculate.
Horsepower and watts
The imperial horsepower is about 745.7 watts, and the electric horsepower is exactly 746 watts [1]. The calculator offers both. A motor's nameplate shows its available shaft power output, not the electrical power input [1], so the output has to be divided by the efficiency to find the power that the motor takes from the supply. For the metric horsepower, about 735.5 watts, convert to kilowatts first [1].
Three-phase voltage
In a three-phase system, the amplitude of the voltage between two phases is √3, about 1.732, times the voltage of a single phase [2]. The line voltage, which is what a nameplate states, is the voltage between two lines. A motor on a 460 volt supply sees 460 volts between its lines, and about 266 volts from each line to the neutral point.
The formula
The current in each line is I = P_in ÷ (√3 × V × PF), where P_in is the electrical input power, V the line voltage and PF the power factor. The input power is the output divided by the efficiency. The pages that we read do not state this formula, so it is a standard relation of ours. For a three-phase load the real power is √3 times the line voltage, times the line current, times the power factor.
A worked example
A 10 horsepower motor has a shaft output of 7,457 watts. With an efficiency of 90 percent, the input is 8,285.6 watts. On 460 volts with a power factor of 0.85, the current is 8,285.6 ÷ (1.732 × 460 × 0.85), which is 12.2 amperes. A 5 horsepower motor on 230 volts, with an efficiency of 85 percent and a power factor of 0.8, draws 13.8 amperes. These are our own calculations.
Efficiency and power factor
The efficiency is the ratio of the mechanical output power to the electrical input power. A typical large motor is more than 85 percent efficient at full load, and a power factor between 0.8 and 0.9 is common at full load, but both figures drop at light load. These ranges come from a summary of the page on induction motors that we could not check word for word, so use the nameplate or the maker's data when you can.
Apparent power
The input power in kilowatts is the real power. The apparent power in kilovolt-amperes is the real power divided by the power factor, and it is what the supply has to carry. For the 10 horsepower example, the real power is 8.29 kilowatts and the apparent power is 9.75 kilovolt-amperes. The calculator shows both in the last line.
What the result is not
The result is the full-load current in normal running. A motor draws a much higher current when it starts, often several times the running current, for a short time. The electrical code sets the sizes of wires, breakers and overload protection from its own tables, which may differ from the calculated current, and which take starting and safety margins into account. Always follow the code and a qualified electrician.
Using the calculator
Take the horsepower, voltage, efficiency and power factor from the nameplate. If the efficiency and power factor are not stated, you can try typical values, and compare with the nameplate current. Use the result to check that a supply is big enough, to compare motors or to estimate the energy use, which is the input power in kilowatts times the hours of running.
More worked examples
A 20 horsepower motor has an output of 14,914 watts. At an efficiency of 92 percent the input is 16,211 watts, and on 460 volts with a power factor of 0.86 the line current is 23.7 amperes. A 7.5 kilowatt motor on 400 volts, with an efficiency of 88 percent and a power factor of 0.82, draws 15.0 amperes. These are our own calculations.
Voltage and current
For the same power, the current is inversely proportional to the voltage. The same motor on 230 volts draws twice the current that it draws on 460 volts. This is why larger motors are run at higher voltages: the wires can be smaller and the losses lower. Check that the motor is connected for the voltage that your supply provides, since many motors can be wired for more than one.
Checking against the nameplate
Most motors carry a nameplate that states the full-load current. Compare it with the calculated figure. A difference of a few percent is normal, since the efficiency and power factor that you entered are only estimates. A large difference means that one input is wrong, perhaps the voltage or the unit of the rating, so check those first. Use the nameplate current for any real design, and the calculator for planning and for sanity checks.
Common mistakes
- Using the output as the input power. Divide by the efficiency.
- Using the phase voltage. Use the line voltage.
- Forgetting the power factor. It raises the current.
- Sizing wires from the result alone. Follow the electrical code tables.
What next
Use this often? Add Three-Phase to your Home screen.
Frequently asked questions
What is a three-phase motor amperage calculator?
A tool that estimates the current drawn by a three-phase motor at full load.
What is the formula for three-phase motor current?
I = P_out ÷ (√3 × V × efficiency × power factor).
How many watts are in a horsepower?
About 745.7 W for the imperial horsepower, and exactly 746 W for the electric horsepower.
Does the nameplate rating show input or output power?
The shaft output power, not the electrical input.
Can I size a breaker from this result?
No. Use the electrical code tables and a qualified electrician.