Wire Size Calculator

Use this wire size calculator to find the smallest copper AWG wire for a circuit from its voltage, current and length, checking both ampacity at 60, 75 or 90 °C and voltage drop, in feet or metres.

Restored your last values ·

Enter the circuit's voltage, current and one-way length. The calculator picks the smallest copper AWG size whose ampacity covers the current and whose voltage drop stays within your limit.

Everything is worked out in your browser. Nothing you type is sent anywhere.

Smallest copper wire size

–

Enter the voltage, current and length, then press Calculate.

See full result

This wire size calculator finds the smallest copper wire gauge for a circuit. Enter the voltage, the current the load draws and the one-way length of the run, in feet or metres, and the wire size calculator checks two things: that the wire's ampacity can carry the current, and that the voltage drop along the run stays within your limit. It shows the size each rule needs and recommends the larger, from 14 AWG up to 4/0 AWG.

How to use the wire size calculator

  1. Choose feet or metres for the length.
  2. Choose DC or single-phase, or three-phase.
  3. Pick the insulation temperature rating of the wire.
  4. Enter the voltage, the load current and the one-way length from the panel to the load.
  5. Set the maximum voltage drop, or leave it at 3%, then press Calculate.

Ampacity: will the wire carry the current?

Every size of wire can only carry so much current before its insulation gets too hot. That limit is its ampacity, and it depends on the insulation's temperature rating. The calculator uses ampacities for insulated copper conductors rated 60, 75 and 90 °C, with no more than three current-carrying conductors in a raceway, cable or the earth at an ambient temperature of 30 °C, as tabulated from the US National Electrical Code. The maximum overcurrent protection allowed for a wire may set a lower limit, so for 14, 12 and 10 AWG the calculator never goes above the 60 °C figures of 15, 20 and 30 amps.

Voltage drop: will enough voltage reach the load?

A long run of thin wire wastes voltage, so equipment at the far end gets less than the supply. The drop depends on the wire's resistance, the current and the length. For DC and single-phase circuits the current goes out and back, so the drop is 2 × length × current × resistance per foot; for three-phase it's √3 × length × current × resistance. The calculator uses the resistance of solid copper at 20 °C, so a hot conductor will drop slightly more. The calculator uses a 3% limit unless you enter a different one, so set whatever limit your design or local rules call for.

American wire gauge sizes

AWGDiameterAreaResistanceAmpacity 60/75/90 °C
141.628 mm2.08 mm²2.525 mΩ/ft15 / 20 / 25 A
122.053 mm3.31 mm²1.588 mΩ/ft20 / 25 / 30 A
102.588 mm5.26 mm²0.9989 mΩ/ft30 / 35 / 40 A
83.264 mm8.37 mm²0.6282 mΩ/ft40 / 50 / 55 A
64.115 mm13.3 mm²0.3951 mΩ/ft55 / 65 / 75 A
45.189 mm21.2 mm²0.2485 mΩ/ft70 / 85 / 95 A
26.544 mm33.6 mm²0.1563 mΩ/ft95 / 115 / 130 A
1/08.251 mm53.5 mm²0.09827 mΩ/ft125 / 150 / 170 A
4/011.684 mm107 mm²0.04901 mΩ/ft195 / 230 / 260 A

Smaller gauge numbers mean thicker wire. Sizes larger than 1 AWG are written 1/0, 2/0, 3/0 and 4/0.

Worked examples

Say you're running a 240 V single-phase circuit for a 40 A load, 100 feet from the panel, with 60 °C wire. For the current, 8 AWG is the smallest size, at 40 amps. Its voltage drop is 2 × 100 × 40 × 0.6282 mΩ, about 5.03 V or 2.09%, under 3%, so 8 AWG does both jobs. Now take a 120 V, 20 A circuit 150 feet long. For the current 12 AWG is enough, but its drop would be about 9.5 V, almost 8%. To stay within 3% you need 6 AWG, which drops about 2.37 V, 1.98%. Long runs are often sized by voltage drop, not current.

Low-voltage and metric runs

Low-voltage DC circuits, such as 12 V lighting, solar or vehicle wiring, are where voltage drop matters most, because a few volts lost is a large share of the supply. A 12 V load drawing 20 A at 20 feet only needs 12 AWG for the current, but that size would drop far more than 3%, so the calculator recommends 6 AWG, which drops about 0.32 V, 2.63%. If you measure in metres, choose Metric: a 230 V single-phase circuit of 16 A running 30 metres needs 12 AWG, which carries 20 A and drops about 5 V, 2.18%. The recommended size is still given in AWG, with its diameter and area in millimetres so you can compare it with metric cable.

Stranded wire and AC

The diameters in the table are for solid wire. Stranded wire of the same gauge has the same copper cross-section, worked out from the equivalent area, so its resistance and the calculator's result are the same, although the cable is slightly thicker overall. The figures assume DC or AC at 60 Hz or less and don't take skin effect into account.

Three-phase circuits

In a balanced three-phase circuit the voltage drop factor is √3, about 1.73, instead of 2, so the same wire drops less voltage than in a single-phase circuit at the same current. For a 480 V three-phase load of 100 A at 200 feet with 60 °C wire, current sets the size at 1 AWG, which drops only about 4.3 V, under 1%.

Common mistakes

  • Entering the round-trip length. Enter the one-way distance; the calculator doubles it for single-phase.
  • Ignoring voltage drop on long runs. A wire that's safe for the current can still drop too much voltage.
  • Choosing a higher temperature rating than your wire has. Use the rating printed on the insulation.
  • Forgetting aluminium is different. These figures are for copper only.

Tips

  • Measure the actual route of the cable, not the straight-line distance.
  • Choose one size up when you expect to add load later.
  • Check the result against your local electrical code before buying cable.

What next

Use this often? Add Wire Size to your Home screen.

Frequently asked questions

What size wire do I need for 40 amps at 100 feet?

At 240 V single-phase with 60 °C copper wire, 8 AWG: it carries 40 A and drops about 2.09%.

How does the wire size calculator choose the size?

It finds the smallest size whose ampacity covers the current and the smallest whose voltage drop stays within your limit, then recommends the larger.

What voltage drop limit does the wire size calculator use?

3% unless you enter another limit. Set the limit your design or local rules require.

Why is 14 AWG limited to 15 amps here?

The maximum overcurrent protection for small wires may set a lower limit than the 75 or 90 °C ampacity, so the calculator uses the 60 °C figures for 14, 12 and 10 AWG.

Does the wire size calculator work in metres?

Yes. Choose Metric to enter the length in metres; the result is the same AWG size.