Power Factor Calculator

Use this power factor calculator to find the power factor, phase angle and kvar from P, S, Q, voltage and current, and estimate the capacitor needed to correct it.

Restored your last values ·

Choose which two values you know. You get the power factor, the phase angle and the real, reactive and apparent power. Add a target power factor to see the capacitor kvar needed, and a voltage and frequency to see the capacitance.

Everything is worked out in your browser. Nothing you type is sent anywhere.

–

–

Choose what you know and fill in the boxes, then press Calculate.

See full result

A power factor calculator finds the ratio between the real power that does work and the apparent power that a circuit draws. Enter any two of the related values, such as the real and apparent power, or the voltage, current and real power, and it gives the power factor, the phase angle and the reactive power, and can estimate the capacitor needed to correct a low power factor.

How to use the power factor calculator

  1. Choose what you know.
  2. Choose single phase or three phase if you use voltage and current.
  3. Enter the values in kW, kVA, kvar, volts or amps as labelled.
  4. Add a target power factor for the correction, then press Calculate.

What power factor is

Wikipedia defines the power factor as the ratio of the real power absorbed by the load to the apparent power flowing in the circuit, PF = P ÷ |S| [1]. For sinusoidal waveforms the power factor equals cos φ, where φ is the phase angle between the voltage and the current [2]. A power factor of 1 means that all the power does work; a lower figure means that part of the current is wasted in going to and fro.

The power triangle

Real power P, reactive power Q and apparent power S form a right triangle, S² = P² + Q² [2]. Wikipedia writes S = P + jQ and gives the reactive power as Q = P tan(arccos pf) [1]. The calculator uses these relations. Give it any two values that fix the triangle, and it finds the rest: the power factor, the angle, and the three powers. Real power is in kilowatts, reactive power in kilovars and apparent power in kilovolt-amperes.

Starting from P and S

With a real power of 80 kilowatts and an apparent power of 100 kilovolt-amperes, the power factor is 80 ÷ 100 = 0.8. The phase angle is the arc cosine of 0.8, 36.87 degrees, and the reactive power is the square root of 100² minus 80², which is 60 kilovars. This is our own example. The other modes reach the same triangle from P and Q, from P and the power factor, from S and the power factor, or from an angle.

Using voltage and current

The apparent power is the product of the RMS voltage and the RMS current, S = I × V for a single phase [2]. In the voltage mode, enter the voltage, the current and the real power measured by a wattmeter. For a single phase supply, S = V × I ÷ 1,000 kilovolt-amperes. For a three phase supply, we use S = √3 × V × I ÷ 1,000 with the line voltage and line current, which is standard three phase arithmetic and our own working. 230 volts at 100 amps and 18 kilowatts gives 0.783.

Leading and lagging

Wikipedia explains that inductive loads, such as motors, draw reactive power with the current lagging behind the voltage, and capacitive loads supply reactive power, with the current leading [1]. The calculator assumes an inductive load, the usual case for a low power factor, and says so in the result. The size of the power factor is the same for lagging and leading loads; only the direction of the reactive power differs.

Why a low power factor costs

Wikipedia gives an example: to deliver 1 kilowatt at a power factor of 0.2, 5 kilovolt-amperes must be transferred. At a power factor of 0.7, the apparent power is 1.4 times the real power, the line current is 1.4 times as large and losses in the circuit are about doubled [1]. This is why utilities charge for a poor power factor in some tariffs, and why plants correct it.

The correction method

To correct a power factor, you measure the true power, find the apparent power from voltage and current, divide to get the power factor, find the angle, find the reactive power, and add a capacitor or an inductor that offsets it. Wikipedia explains that capacitors or inductors can offset the reactive effects of linear loads [3]. The calculator therefore uses the standard relation that follows from the triangle: Qc = P (tan φ₁ − tan φ₂), our own working.

A correction example

Take the 80 kilowatt load at a power factor of 0.8 and a target of 0.95. The tangent of the starting angle is 0.75 and that of the target angle is 0.3287, so the capacitors must supply 80 × 0.4213 = 33.7 kilovars. The apparent power falls from 100 to 84.2 kilovolt-amperes and the line current to 84.2 percent of its old value, because the real power stays the same. The calculator prints these figures.

The capacitance

To turn kilovars into microfarads we need the voltage and the frequency. For one capacitor across a single phase supply, C = Qc ÷ (2π f V²). For three capacitors connected in delta across a three phase supply, each is C = Qc ÷ (3 × 2π f V²) with the line voltage. These are our own working from the reactance of a capacitor, since Wikipedia gives the impedance of a capacitor as 1 ÷ (jωC) [4]. For 33.7 kilovars at 400 volts and 50 hertz, each delta capacitor is about 224 microfarads.

Limits and safety

The correction formulas assume a steady inductive load, a sine wave and capacitors connected across the load. Loads that draw distorted currents, variable loads and circuits with harmonics need a proper study, as correction capacitors can create resonant conditions with the supply [3]. Overcorrection gives a leading power factor. Use the results only as a first estimate, and have the capacitor bank chosen, protected and installed by a qualified electrician following the local code.

Common mistakes

  • Mixing kW and kVA. Real power is in kW, apparent power in kVA.
  • Using phase voltage for a three phase supply. Use the line voltage.
  • Correcting a load to a power factor of exactly 1. This risks overcorrection.
  • Sizing capacitors without a harmonics check. They can resonate.

What next

Use this often? Add Power Factor to your Home screen.

Frequently asked questions

What is a power factor calculator?

A tool that finds the ratio of real to apparent power and the related reactive power and phase angle.

How do you calculate the power factor?

Divide the real power in kW by the apparent power in kVA, which equals the cosine of the phase angle.

How do you correct a low power factor?

Add a capacitor that supplies the reactive power, Qc = P (tan φ₁ − tan φ₂).

What is a good power factor?

The closer to 1 the better; at 0.7, the line current is 1.4 times the current at unity.

Is a lagging power factor the same as a leading one?

The value is the same; lagging means an inductive load and leading a capacitive one.