The CFM calculator works out how much airflow, in cubic feet per minute (CFM), a space needs. Use it three ways: enter a room’s size and the number of air changes per hour you want, size a bathroom exhaust fan, or size a kitchen range hood. Fan and hood guidelines come from the Home Ventilating Institute (HVI), the US body that certifies ventilation products. For example, a 12 × 14 ft room with an 8 ft ceiling needs 89.6 CFM to change its air 4 times an hour.
The CFM formula
Airflow and room volume are linked by the number of air changes per hour (ACH), which says how many times the whole volume of air is replaced each hour:
- CFM = room volume (cubic feet) × ACH ÷ 60
- ACH = CFM × 60 ÷ room volume
You divide by 60 because CFM is per minute and ACH is per hour. The American Industrial Hygiene Association’s air-change calculator uses the same relationship. Room volume is length × width × ceiling height.
How to use the CFM calculator
- Pick a mode: Room (air changes), Bathroom fan or Range hood.
- Choose US or metric units. US gives CFM; metric gives cubic meters per hour, with liters per second and the CFM equivalent in the table.
- Room: enter the length, width and ceiling height, and the air changes per hour you’re aiming for.
- Bathroom fan: enter the floor size. If the room is over 100 sq ft, also enter the number of toilets, showers, tubs and jetted tubs.
- Range hood: enter the width of the range and tick the box if it’s on an island.
Worked example: air changes in a room
A bedroom 12 ft long and 14 ft wide with an 8 ft ceiling holds 12 × 14 × 8 = 1,344 cubic feet. To replace that air 4 times an hour, the fan or air handler must move 1,344 × 4 ÷ 60 = 89.6 CFM, which is about 152 cubic meters per hour or 42.3 liters per second. Turn it around and a 300 CFM fan in the same room would give 300 × 60 ÷ 1,344 = 13.4 air changes an hour.
Bathroom exhaust fan CFM
HVI recommends these intermittent ventilation rates for bathrooms:
| Bathroom | Recommended rate |
|---|---|
| Up to 100 sq ft | 1 CFM per sq ft of floor, at least 50 CFM |
| Over 100 sq ft | 50 CFM each for a toilet, shower and bathtub; 100 CFM for a jetted tub |
So an 8 × 10 ft bathroom (80 sq ft) needs an 80 CFM fan, and a small 5 × 8 ft bathroom still needs the 50 CFM minimum. A 10 × 12 ft bathroom (120 sq ft) with a toilet, a shower and a tub needs 50 + 50 + 50 = 150 CFM. HVI also says an enclosed toilet should have its own fan, and that ventilation should keep running for at least 20 minutes after each use.
Range hood CFM
HVI’s range hood rates are based on the width of the range:
| Range location | Recommended per foot of range | Minimum per foot |
|---|---|---|
| Against a wall | 100 CFM | 40 CFM |
| On an island | 150 CFM | 50 CFM |
A standard 30-inch (2.5 ft) range against a wall therefore needs 250 CFM, with 100 CFM as the minimum. A 36-inch island cooktop needs 3 × 150 = 450 CFM. HVI notes that hoods that recirculate air instead of venting outside don’t provide real ventilation, and that for professional-style cooktops you should follow the manufacturer’s advice.
Choosing a fan
- Look for the certified rating. HVI-certified fans and hoods show tested airflow on the label, which is more reliable than uncertified claims.
- Allow for ducts. Long duct runs, elbows and small ducts reduce real airflow, so a fan’s rating is a best case.
- Check noise. A fan that is too loud often gets switched off early. Compare sone ratings as well as CFM.
- Make-up air. HVI says bathroom doors need at least 3/4 inch of clearance to the floor so replacement air can get in.
Whole-house ventilation
For continuous fresh air from a heat or energy recovery ventilator, HVI suggests 0.35 air changes per hour for the whole occupied volume of the home. You can use the room mode for this: enter the home’s total floor dimensions and ceiling height with 0.35 air changes. To size heating or cooling equipment instead, use the BTU calculator or the AC tonnage calculator.
Choosing air changes per hour
There is no single right number of air changes for every room. The right rate depends on what the room is used for, how many people are in it and what is producing moisture, smells or fumes. Spaces such as workshops, garages and hobby rooms with dust or fumes usually need more air changes than a bedroom. If an engineer, a code or an equipment maker gives you a target ACH or CFM for your space, use that. Otherwise, the bathroom and range hood modes give HVI’s recommended rates for the two rooms where most homes need exhaust fans.
Metric units
In metric mode, enter sizes in meters. The calculator shows airflow in cubic meters per hour, with liters per second and the CFM figure in the table, so you can compare with fans rated in either system.
The results are guidelines for planning. Building codes and equipment manufacturers may set their own requirements, so check them before you buy or install a fan.
What next
Use this often? Add CFM to your Home screen.
Frequently asked questions
What formula does the CFM calculator use?
CFM = room volume in cubic feet × air changes per hour ÷ 60. A 1,344 cubic foot room at 4 air changes an hour needs 89.6 CFM.
How many CFM do I need for a bathroom fan?
HVI recommends 1 CFM per square foot for bathrooms up to 100 sq ft, with a 50 CFM minimum. Larger bathrooms add 50 CFM per toilet, shower and tub and 100 CFM per jetted tub.
How many CFM does a range hood need?
HVI recommends 100 CFM per linear foot of range against a wall and 150 CFM per foot on an island, so a 30-inch wall range needs 250 CFM.
How do I convert CFM to cubic meters per hour?
Multiply by about 1.699. One CFM is also about 0.472 liters per second.