Breaker Size Calculator

Use this breaker size calculator to estimate the circuit breaker for one appliance from its power and voltage, with a 25% margin and the next standard size.

Restored your last values ·

W
V
A

Choose the circuit type, then enter the appliance power and the voltage. For AC, add the power factor. You get the load current, the minimum breaker current and the next standard breaker size.

Everything is worked out in your browser. Nothing you type is sent anywhere.

–

–

Choose what to find, fill in the boxes and press Calculate.

See full result

A breaker size calculator estimates which circuit breaker suits an appliance. Enter the power and the voltage, and it works out the load current, adds a 25% margin and rounds up to the next standard breaker size. It is an estimate for one appliance, so ask a licensed electrician before you install anything.

How to use the breaker size calculator

  1. Choose the circuit type: DC, AC single phase or AC three phase.
  2. Enter the power in watts and the voltage.
  3. For AC, enter the power factor, or leave it blank for 1.
  4. Press Calculate.

The load current

Wikipedia defines power factor as the ratio of real power to apparent power, and apparent power as the product of the rms current and the rms voltage [3]. Rearranged, the current is the power divided by the voltage and the power factor. For DC, the current is the power divided by the voltage. For three-phase AC, the line-to-line voltage is the square root of 3 times the line-to-neutral voltage [4], so the current is the power divided by the voltage, the power factor and the square root of 3. That last step is our own working. The calculator uses the line-to-line voltage for three-phase circuits.

The 25% margin

A breaker should be sized for at least 125% of the load. This is the same as keeping the load at no more than 80% of the breaker rating, which is our own arithmetic. EC&M, a trade magazine, summarises the rule in the National Electrical Code: the overcurrent device must be at least 125% of the continuous load, with sections 210.20(A) and 215.3 [2]. We read the magazine, not the code itself.

Continuous and other loads

The tool's default applies the 25% margin to every load. EC&M describes the margin as applying to the continuous load [2]. The tool therefore has two settings. The default is 125%. The 100% setting for a load that is not continuous, with no margin, is our own reading of the magazine. If in doubt, keep 125%, which is the safer figure.

Standard sizes

Breakers are sold in standard sizes. IAEI lists the standard ratings in the code as 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400 and larger sizes up to 6,000 amps [1]. The tool uses the sizes up to 400 amps and picks the first at or above the minimum current. The same article says the code allows the next higher standard rating to be used for devices of 800 amps or less, if the conductor ampacity does not match a standard size and other conditions are met [1].

A single-phase example

A dishwasher of 1,800 watts at 230 volts and a power factor of 0.88 draws 1,800 ÷ (230 × 0.88) = 8.89 amps. With the 25% margin the minimum is 11.12 amps, and the next standard size is 15 amps. A different rounding order can print 11.11 for the margin. The 15 amp breaker would carry 59% of its rating.

A microwave example

A microwave of 1,000 watts at 230 volts and a power factor of 0.72 draws 6.04 amps. The minimum breaker current is 7.55 amps, and the smallest size on the list, 15 amps, is chosen. The tool treats 15 amps as the lowest size, as the list does. It does not say that every circuit should use a 15 amp breaker, because the rest of the circuit matters.

A three-phase example

Take 10,000 watts at 400 volts, a power factor of 0.9 and three phases. The current is 10,000 ÷ (400 × 0.9 × 1.732) = 16.04 amps. With the margin, the minimum is 20.05 amps, and the next standard size is 25 amps. This three-phase example is our own working. The same formula is used by the tool.

The largest load

The second mode turns the problem around. For a breaker of a given rating, the largest load is the rating divided by 1.25, times the voltage and the power factor. This is our own rearrangement. A 15 amp breaker at 230 volts and a power factor of 0.88 supports 12 amps, or 2,428.8 watts. The tool does not mix this with the full-rating figure, which ignores the margin.

Wire and other limits

A breaker protects the wire, so the wire must be rated for at least the breaker's current. The tool does not check the wire size, the voltage drop, the temperature, motor loads, which have separate rules, or local code. It handles one appliance and not the whole panel. None of these points are covered here, so do not use the result as a design.

Using the calculator

Choose the circuit type and the margin, enter the power and the voltage and press the button. Read the recommended breaker and the share of the rating that the load takes. Use it to compare appliances or to check a nameplate. Then show the figures to a licensed electrician, who will check the wire and the code for your area.

Reading the nameplate

Most appliances carry a nameplate that gives the power in watts or the current in amps, the voltage, and sometimes the power factor. If the plate gives the current, you can skip the first step: multiply it by the margin and choose the next standard size. If it gives a watt figure only, use the calculator for the current. When a plate shows a range, use the highest figure, since a breaker must cope with the largest load that the appliance can draw. These are our own practical notes and they are not from the sources.

Several appliances on one circuit

This tool handles one appliance. For several on a circuit, the currents add, which is our own working, and the breaker has to suit the total. Add the load currents first, then apply the margin. We give no whole-panel method, so ask an electrician about the service as a whole.

Common mistakes

  • Forgetting the power factor on an AC load. Check the nameplate, or use 1 if none is given.
  • Using the wrong voltage for three phase. Use the line-to-line voltage.
  • Picking a breaker that is too large for the wire. The wire must carry at least the breaker's current.
  • Treating the result as a design. Ask a licensed electrician.

What next

Use this often? Add Breaker Size to your Home screen.

Frequently asked questions

What is a breaker size calculator?

A tool that estimates the circuit breaker for an appliance from its power, voltage and power factor.

What size breaker do I need for 1,800 watts at 230 volts?

With a power factor of 0.88, the current is 8.89 amps, the minimum with the 25% margin is 11.12 amps and the next standard size is 15 amps.

What is the 125% rule for a breaker?

The breaker should be at least 125% of the load, which keeps the load at 80% of the rating or less.

Does the breaker size calculator choose the wire?

No. The wire must be rated for at least the breaker's current, and an electrician should check it.

What is the largest breaker the breaker size calculator lists?

400 amps. Larger sizes need a licensed electrician or an engineer.