A voltage regulation calculator tells you how much a supply voltage changes between no load and full load, as a ratio and as a percentage. Enter the two voltages and you get the usual percent regulation and the version divided by the no-load voltage. It also works out line regulation and load regulation from two measured changes.
How to use the voltage regulation calculator
- Choose voltage regulation, line regulation or load regulation.
- For voltage regulation, enter the no-load and full-load voltage.
- For the other two, enter the change in the output voltage and the change in the input voltage or load current.
- Press Calculate.
What voltage regulation means
Voltage regulation measures how well a supply holds its voltage when the load changes. The no-load voltage is measured at the terminals when nothing is connected, and the full-load voltage is measured when the full load is drawing current [1]. Wikipedia gives the percent regulation as the difference between the two voltages divided by the full-load voltage, times 100 [1]. A low figure means a stiff supply, and an ideal one shows no change at all [1].
The two formulas
The tool shows two ratios. The step-down ratio is the no-load voltage minus the full-load voltage, divided by the no-load voltage. The step-up ratio is the same difference divided by the full-load voltage, which is the percent regulation that Wikipedia gives [1]. Each ratio times 100 is the percentage change. The full-load version is the headline.
A worked example
Take a supply that reads 230 volts with no load and 220 volts at full load. The difference is 10 volts. Divided by 220 it gives 0.04545, or 4.545 percent; divided by 230 it gives 0.04348, or 4.348 percent. Rounded to three digits these are 0.0435 and 0.0454. A second example, 140 volts at no load and 120 volts at full load, gives 14.3 percent on the no-load basis (20 ÷ 140) and 16.7 percent on the full-load basis.
Linear and switching regulators
A linear regulator can only step the voltage down, since its output must always be lower than its input, and it dissipates the difference as waste heat [2]. A switching regulator switches its pass element between full on and full off, can step the voltage down or up, and is much more efficient [3]. This is why the tool gives a step-down and a step-up version of the ratio. Which one you want depends on how the regulation figure is quoted for your device.
Line regulation
Line regulation is the change in output voltage for a change in the input voltage, ΔV_out divided by ΔV_in. Wikipedia describes it as the ability to hold a constant output voltage regardless of changes to the input voltage [1]. If the output moves by 0.01 volts when the input moves by 2 volts, the line regulation is 0.005, or 5 millivolts per volt. An ideal regulator scores zero.
Load regulation
Load regulation is the change in output voltage for a change in load current, ΔV_out divided by ΔI_load. It can also be written as the no-load voltage minus the full-load voltage, divided by the change in load current. Wikipedia describes it as the ability to hold a constant output voltage regardless of the size of the load [1]. An output that falls by 50 millivolts when the load rises by 1 amp has a load regulation of 0.05 volts per amp.
Transformers and power lines
Wikipedia applies the same definition to a transformer, where the real windings cause a voltage change when current flows, so the regulation is not zero and must be allowed for in use. It also applies it to a supply line, where the receiving end is open circuit at no load [1]. The page gives no separate transformer formula, so the tool does not add one: enter the no-load and full-load secondary voltages you measured, and the same calculation applies.
Service voltage and tolerances
Wikipedia mentions service voltages such as 220 or 240 volts, with tolerance bands of about plus or minus 5 or 10 percent [1]. You can use the regulation figure to see whether a supply stays inside the band you need. A 4.5 percent drop fits within a 5 percent band but leaves little margin for any other loss, such as the drop in a long cable.
Negative values and limits
If the full-load voltage is higher than the no-load voltage, the regulation comes out negative, and the tool says the voltage rises under load. The two voltages must be above zero. The line and load modes allow any change, but the input change or the current change cannot be zero, because the result divides by it. Wikipedia gives no worked numbers for these formulas, so every example here is our own working.
Limits of the calculator
The tool uses the simple ratio of two readings. It does not model the source impedance, the power factor of the load or the temperature, which all affect real regulation. Wikipedia describes a short-line model with a line and load impedance, which this page does not use [1]. Treat the answer as a figure to compare supplies, and take your readings at the terminals under the conditions you care about.
Common mistakes
- Dividing by the wrong voltage. Percent regulation uses the full-load voltage; the buck ratio uses the no-load one.
- Taking readings away from the terminals. Cable drop then adds to the result.
- Mixing line and load regulation. One is per volt of input, the other per amp of load.
- Entering a zero change. Line and load regulation divide by the input change or the current change.
What next
Use this often? Add Voltage Regu to your Home screen.
Frequently asked questions
What is a voltage regulation calculator?
A tool that compares the no-load and full-load voltage of a supply and gives the change as a ratio and a percentage.
How do you calculate percent voltage regulation?
Subtract the full-load voltage from the no-load voltage, divide by the full-load voltage and multiply by 100.
What is the difference between step-down and step-up regulation?
Step-down divides the difference by the no-load voltage; step-up divides it by the full-load voltage.
What are line regulation and load regulation?
Line regulation is the output change per unit input change; load regulation is the output change per unit load current change.
Can the regulation be negative?
Yes. If the voltage rises under load, the no-load voltage is lower than the full-load voltage and the result is negative.