Effectiveness-NTU Calculator

Use this effectiveness-NTU calculator to find the effectiveness of a counter-flow, parallel-flow or cross-flow heat exchanger from UA and the heat capacity rates, and the heat transferred.

Restored your last values ·

Choose the flow arrangement and enter UA and the heat capacity rates of the hot and cold fluids. Add the inlet temperatures to get the heat transferred and the outlet temperatures.

Everything is worked out in your browser. Nothing you type is sent anywhere.

–

–

Enter UA and the two heat capacity rates, then press Calculate.

See full result

An effectiveness-NTU calculator finds how effective a heat exchanger is, from its UA value and the heat capacity rates of the two fluids. Choose counter-flow, parallel-flow or cross-flow, and it gives the number of transfer units, the effectiveness and, with the inlet temperatures, the heat transferred and the outlet temperatures.

How to use the effectiveness-NTU calculator

  1. Choose the flow arrangement.
  2. Enter UA and the heat capacity rates of both fluids.
  3. Add the inlet temperatures for the heat transferred.
  4. Press Calculate.

The method

The effectiveness-NTU method is used to find the heat transfer of an exchanger when the outlet temperatures are not known. The number of transfer units is NTU = UA ÷ C_min, the ratio of the heat capacity rates is C_r = C_min ÷ C_max, and the effectiveness is ε = Q ÷ Q_max [1]. The effectiveness depends on the NTU and C_r, and on the flow arrangement [1].

Maximum heat transfer

The most that an exchanger could transfer is Q_max = C_min (T_h,in − T_c,in), which would be reached by an infinitely long counter-flow exchanger [1]. The real heat transfer is therefore Q = ε C_min (T_h,in − T_c,in) [1]. Once the effectiveness is known from the formulas below, the heat transfer and the outlet temperatures follow without iteration.

Counter-flow

For a counter-current exchanger, ε = [1 − exp(−NTU (1 − C_r))] ÷ [1 − C_r exp(−NTU (1 − C_r))] [1]. When the capacity rates are equal, C_r = 1, this becomes ε = NTU ÷ (1 + NTU) [1]. Counter-flow is the most effective arrangement for a given NTU. With UA = 1,500 W/K, C_min = 1,000 and C_max = 2,000, NTU is 1.5, C_r is 0.5 and ε is 0.6908.

Parallel-flow

For a parallel-flow exchanger, ε = [1 − exp(−NTU (1 + C_r))] ÷ (1 + C_r) [1]. For the same data it gives 0.5964, lower than the counter-flow value of 0.6908. In parallel flow, the two fluids come close in temperature at the outlet, which limits the heat transfer, and the effectiveness can never exceed 1 ÷ (1 + C_r).

Cross-flow

For a cross-flow exchanger with both fluids mixed, the page gives ε = [1 ÷ (1 − exp(−NTU)) + C_r ÷ (1 − exp(−NTU C_r)) − 1 ÷ NTU]⁻¹ [1]. With the same data the effectiveness is 0.6377, between the parallel and the counter-flow values. The calculator covers this case. The unmixed and the one-mixed forms are not included, and neither are shell-and-tube arrangements.

A worked example

A hot fluid with a heat capacity rate of 1,000 W/K enters at 150 degrees Celsius and a cold fluid of 2,000 W/K enters at 30 degrees, in counter-flow with UA = 1,500 W/K. The effectiveness is 0.6908, so Q = 0.6908 × 1,000 × 120 = 82,894 watts. The hot fluid leaves at 150 − 82.894 = 67.1 degrees and the cold fluid at 30 + 41.447 = 71.4 degrees. The example is our own.

Phase change

If one fluid changes phase, as in a boiler or a condenser, its temperature stays fixed and its heat capacity rate is effectively infinite, so C_r is 0. The page then gives ε = 1 − exp(−NTU), whatever the flow arrangement [1]. The calculator uses that expression when C_r is zero, which you can approach by entering a very large heat capacity rate for one fluid.

Why use NTU

The log-mean temperature difference method needs the outlet temperatures, which are often unknown in a design check. The NTU method needs only the inlets and the size of the exchanger. It is therefore the natural way to rate an existing exchanger or to see how its performance changes with the flow rates. Doubling UA does not double the heat transfer, since the effectiveness approaches a limit.

Limits

The results are for steady flow, constant properties, uniform UA and no heat loss to the surroundings. The heat capacity rate of each fluid is its mass flow rate times its specific heat, in watts per kelvin. The calculator takes the rates directly, so work them out first. It does not give the pressure drop, which needs a separate calculation.

Using the calculator

Pick the arrangement and enter UA, then the two capacity rates in any order, since the calculator finds which is smaller. Add the inlet temperatures for the heat rate. To compare designs, switch the arrangement and see how the effectiveness changes. The working line shows the formula that was used.

Sizing an exchanger

To size an exchanger, find the effectiveness that you need and solve for the NTU. For a counter-flow exchanger with C_r = 0.5, an effectiveness of 0.8 needs an NTU of 2.197, which is our own result from inverting the counter-flow formula. With a minimum capacity rate of 1,000 watts per kelvin, UA must be 2,197 watts per kelvin. Try UA values near this in the calculator and see the effectiveness approach 0.8.

Diminishing returns

With C_r = 0.8 and NTU = 1, a counter-flow exchanger has an effectiveness of 0.5254. Doubling UA does not double the heat transfer, since the effectiveness approaches a limit as the NTU rises. This is why a very large exchanger is rarely worth its cost, and designs usually settle on NTU values between about 1 and 3.

Common mistakes

  • Using the wrong C for NTU. Use the smaller capacity rate.
  • Entering flow rates in place of capacity rates. Multiply by the specific heat.
  • Assuming counter-flow in a cross-flow unit. Pick the right arrangement.
  • Expecting more heat from a bigger UA forever. Effectiveness has a limit.

What next

Use this often? Add Effectivenes to your Home screen.

Frequently asked questions

What is an effectiveness-NTU calculator?

A tool that finds the effectiveness of a heat exchanger from NTU and the capacity rate ratio.

What is NTU?

The number of transfer units, UA ÷ C_min.

What is the effectiveness of a counter-flow exchanger when C_r = 1?

NTU ÷ (1 + NTU).

How do I find the heat transferred?

Q = ε C_min (T_h,in − T_c,in).

What if one fluid changes phase?

Then C_r = 0 and ε = 1 − exp(−NTU) for any arrangement.