An LMTD calculator finds the log mean temperature difference of a heat exchanger, the average driving temperature difference between the hot and the cold stream. Enter the four inlet and outlet temperatures and choose counterflow or parallel flow. With a coefficient and an area, it also gives the heat duty.
How to use the LMTD calculator
- Choose US or metric units and the flow arrangement.
- Enter the hot inlet and outlet and the cold inlet and outlet temperatures.
- Optionally enter the overall heat transfer coefficient U and the area A.
- Press Calculate.
What the log mean temperature difference is
In a heat exchanger the temperature difference between the two streams changes along the length of the exchanger, so a simple average is not the right driving force. The log mean temperature difference is defined from the differences at the two ends, A and B, as LMTD = (ΔT_A − ΔT_B) ÷ ln(ΔT_A ÷ ΔT_B), where each difference is taken between the two streams at that end [1]. The calculator uses this formula and names the two differences ΔT₁ and ΔT₂.
Counterflow and parallel flow
The two differences depend on how the streams meet. The two ends are where the streams meet. In parallel flow both streams enter at the same end [1], so ΔT₁ = hot inlet − cold inlet and ΔT₂ = hot outlet − cold outlet. In counterflow they enter from different ends [1], so ΔT₁ = hot inlet − cold outlet and ΔT₂ = hot outlet − cold inlet. The tool shows both values in the result.
A worked example
Take a hot stream cooled from 80 °C to 40 °C and a cold stream heated from 20 °C to 50 °C, in counterflow. Then ΔT₁ = 80 − 50 = 30 °C and ΔT₂ = 40 − 20 = 20 °C, and the log mean is 10 ÷ ln 1.5, about 24.663 °C. This calculator stops at that figure, because it does not apply a correction factor.
Why counterflow beats parallel flow
Wikipedia calls the counter-current design the most efficient, because the average temperature difference along the exchanger is higher [2]. For the same four temperatures, the counterflow value is greater than the parallel one, and since Q = U A LMTD, a counterflow exchanger needs less area for the same heat duty. The calculator shows the other arrangement with every result. With the example above, parallel flow is not even possible, because the cold stream leaves hotter than the hot stream does, which would make the outlet difference negative. The tool tells you so instead of giving a meaningless number.
When the two differences are equal
If ΔT₁ and ΔT₂ are the same, the formula gives zero divided by zero. Wikipedia says the LMTD is then conventionally taken to equal its limit value [1], which is the common value of the two differences. The calculator uses ΔT₁ in that case and says so in the result. Hot 90 and 50 against cold 30 and 70 in counterflow, for instance, gives 20 at both ends and an LMTD of exactly 20.
From the LMTD to the heat duty
The heat transferred is Q = U × A × LMTD, with U the overall heat transfer coefficient and A the area [1]. The Wikipedia article writes the coefficient as α and adds that estimating it can be complicated [1]. The calculator multiplies the three numbers when you fill in both U and A. In metric units, U is in watts per square metre per kelvin, A in square metres and Q in watts. In US units, U is in Btu per hour per square foot per °F, A in square feet and Q in Btu per hour.
Units
A temperature difference of one kelvin equals one degree Celsius, and a difference of one °F is 5/9 of that, so the LMTD is shown in the same unit as the temperatures you enter. There is no offset to deal with, because only differences are used. Choose US to enter Fahrenheit and Btu-based values, or metric to enter Celsius and watt-based values. Do not mix the two systems: if U is in watts per square metre per kelvin, the temperatures must be in °C or K.
What the formula assumes
The method assumes a constant specific heat for both fluids, a constant heat transfer coefficient and a steady state. It does not model a phase change, apart from the special case of condensers and reboilers, and it neglects changes in kinetic and potential energy [1]. For cross-flow exchangers and other more complex geometries, such as baffled shell and tube designs, a correction factor is needed [1]. Treat the result as a first estimate.
Using the result in practice
Once you have the LMTD, you can size an exchanger by dividing the required heat duty by the product of U and the LMTD, to get the area. You can also check an existing exchanger against its rated duty. Compare counterflow with parallel flow to see how much area the better arrangement saves. For a more detailed design, check the exchanger against the manufacturer's data and a heat exchanger design standard, and use measured coefficients rather than textbook guesses.
Common mistakes
- Entering the temperatures in the wrong order. Hot and cold, inlet and outlet must be in the right boxes, or the differences are wrong.
- Using parallel flow for a counterflow exchanger. The result is lower and may be impossible.
- Mixing °C with Btu units. Keep the units consistent.
- Applying the plain LMTD to a cross-flow exchanger. A correction factor is needed.
What next
Use this often? Add LMTD to your Home screen.
Frequently asked questions
What is an LMTD calculator?
A tool that finds the log mean temperature difference of a heat exchanger from the inlet and outlet temperatures of the two streams.
What is the LMTD formula?
LMTD = (ΔT1 − ΔT2) ÷ ln(ΔT1 ÷ ΔT2), with the two end-point temperature differences.
Is counterflow or parallel flow better?
Counterflow gives the larger LMTD for the same temperatures, so it needs less area.
What happens when ΔT1 equals ΔT2?
The formula is undefined, and the LMTD is taken as the common value.
Does this LMTD calculator use a correction factor?
No. It applies to pure counterflow or parallel flow, and cross-flow or multi-pass exchangers need a correction factor.