Use this psychrometric calculator to find the dew point, wet bulb, humidity ratio, enthalpy and virtual temperature of moist air from a temperature and one humidity value.

Restored your last values ·

%

Enter the air temperature and one other known value: the relative humidity, the wet-bulb temperature or the dew point. Add the altitude to correct the air pressure. You get the other humidity values, the humidity ratio, enthalpy and virtual temperature.

Everything is worked out in your browser. Nothing you type is sent anywhere.

–

–

Enter the dry-bulb temperature and one more value, then press Calculate.

See full result

A psychrometric calculator works out the state of moist air from a few readings. Enter the air temperature and either the relative humidity, the wet-bulb temperature or the dew point, with an optional altitude. It gives the other two, the vapour pressures, the humidity ratio, the enthalpy and the virtual temperature.

How to use the psychrometric calculator

  1. Pick the second known value and the units.
  2. Enter the dry-bulb temperature and that value.
  3. Add the altitude if you are not at sea level.
  4. Press Calculate.

Three values fix the state

Wikipedia says that a psychrometric chart works from any three independent parameters, one of which must be the pressure [5]. Here they are the pressure, the dry-bulb temperature and one of the wet-bulb temperature, relative humidity or dew point. The calculator takes the dry-bulb temperature and one of the other three, and gets the pressure from the altitude. That covers the usual readings from a thermometer, a hygrometer or a sling psychrometer.

Vapour pressure

The saturation vapour pressure is Ps = 6.112 exp(17.67 T ÷ (T + 243.5)) in hectopascals, with T in degrees Celsius. The Wikipedia dew point article lists the constants 6.112, 17.67 and 243.5 for this form, with a stated maximum error of 0.1 percent from −30 to 35 °C [1]. The partial pressure is the relative humidity times Ps.

Dew point

The dew point comes from the partial pressure: Tdp = 243.5 ln(Pv/6.112) ÷ (17.67 − ln(Pv/6.112)) [1]. At 25 °C and 63.61 percent, the calculator gives 17.63 °C. In dew point mode, the calculator runs the formula backwards to get the humidity.

Humidity ratio

The humidity ratio is ω = 0.6219 Pv ÷ (Pa − Pv), the mass of water vapour for each unit mass of dry air. The National Weather Service writes the mixing ratio as 621.97 e ÷ (P − e) in grams per kilogram [2], which is the same quantity; the tool uses the rounded coefficient 0.6219. At 25 °C, 63.61 percent and 100 m, the calculator gives 0.01277 kg/kg. The tool uses the humidity ratio formula only in the direction above.

Air pressure

Wikipedia's barometric formula, which follows the U.S. Standard Atmosphere, gives the pressure in a layer where temperature changes linearly with height [4]. The tool uses P(h) = P₀(1 − L h ÷ T₀)^(g M ÷ (R₀ L)) with g = 9.8, L = 0.00976, M = 0.028969 and R₀ = 8.314, and the standard sea-level values 288.15 K and 101,325 Pa. This gives 1,001 hPa at 100 m. The standard atmosphere uses a lapse rate of 0.0065 K per metre [4], so treat the tool's pressure as a model.

Wet-bulb temperature

The tool uses the empirical wet-bulb formula published by Roland Stull in 2011, with coefficients 0.151977, 8.313659, 0.00391838, 0.023101, 1.676331 and 4.686035, for T and Tw in °C and the humidity in percent. It is meant for humidity from 5 to 99 percent and temperature from −20 to 50 °C. For 25 °C and 40 percent it gives 16.384 °C.

Why not the psychrometer equation

The tool does not use a psychrometer equation, because we could not confirm its wet-bulb coefficient against a primary source. In wet-bulb mode the calculator inverts the Stull formula for the humidity instead.

Enthalpy and saturation

The enthalpy is h = 1.006 T + ω(2499.86 + 1.84 T) with T in °C, which gives 57.66 for 25 °C at 63.61 percent and 100 m. We read the unit as kilojoules per kilogram of dry air, which is our inference from the coefficients. The degree of saturation is ω divided by the humidity ratio at saturation.

Virtual temperature

Wikipedia gives the linear approximation Tv ≈ T(1 + 0.608 w), with temperature in kelvin and the mixing ratio w in g/g [3]. The tool rounds the coefficient to 0.61 and applies it to the humidity ratio. For 25 °C at 63.61 percent and 100 m, the virtual temperature is 27.32 °C. The mixing ratio of air is the same as the humidity ratio here, so the mixing ratio and relative humidity rows are covered by this page.

Limits

The air pressure is a model, the wet bulb is an approximation, and the vapour pressure formula is best between −30 and 35 °C [1]. Outside the stated ranges the tool says so. For air-conditioning design, ventilation or drying, use a full psychrometric chart or the ASHRAE method. For a day-to-day check of humidity, comfort or dew, the numbers here are close enough.

A second example

Take air at 25 °C and 40 percent relative humidity at sea level. The calculator gives a dew point of 10.48 °C, a wet bulb of 16.38 °C, a humidity ratio of 0.007875 kg/kg and an enthalpy of 45.2 kJ per kg of dry air; the wet bulb is the 16.384 °C that the Stull formula gives for these inputs. Entering that wet bulb in the wet-bulb mode returns 40 percent. In US mode the same air is 77 °F, with a dew point of 50.86 °F. The temperatures are shown in both scales, and the altitude can be given in feet or metres. At 3,000 m the station pressure falls, and the humidity ratio of the same air rises, because less dry air shares the same vapour pressure, which follows from the humidity ratio formula above [2].

Common mistakes

  • Entering the wet bulb as the dry bulb. The dry bulb is the plain air temperature.
  • Typing 0.6 for 60 percent. Humidity is in percent.
  • Forgetting the altitude. It changes the humidity ratio.
  • Using a dew point above the air temperature. That is not possible.

What next

Use this often? Add Psychrometri to your Home screen.

Frequently asked questions

What is a psychrometric calculator?

A tool that finds the properties of moist air, such as dew point, wet bulb and humidity ratio, from a few readings.

How many values fix the state of the air?

Three: the pressure, the dry-bulb temperature and one of the relative humidity, wet-bulb temperature or dew point.

What is the humidity ratio?

The mass of water vapour per unit mass of dry air, 0.6219 Pv ÷ (Pa − Pv).

How is the wet-bulb temperature found?

With the Stull formula from the temperature and the relative humidity, accurate from 5 to 99 percent and −20 to 50 °C.

What is virtual temperature?

The temperature that dry air would need for the same density, about Tv = T(1 + 0.61 w) in kelvin.

What went wrong?